A hollow core slab has no code sound rating. The room pair does.
That is the whole problem. A specifier picks a slab depth, reads a laboratory number from a product sheet, and writes it into the spec. The code then measures something else: the separation as built, with the walls, the junctions and the penetrations counted against it. The slab is one path out of several.
This article covers 203 mm (8 in.) grouted precast concrete hollow core floors in multi-unit residential buildings in Alberta: what the code asks for, what the published ratings are, what the topping changes, and what we need to quote.
The short answer: the requirement is ASTC 47, and it is a field quantity
Alberta builds to the National Building Code – 2023 Alberta Edition. The first printing was declared in force 1 May 2024, replacing the 2019 Alberta Edition, which ran from 1 December 2019. A second printing was published 17 August 2026.
Two numbers govern separations between dwelling units. A laboratory sound transmission class of 50 has been the requirement since the 1990 model code. The 2015 model code added an apparent sound transmission class of 47 as the route that accounts for the finished building, and the acoustical provisions carried into the 2020 model code without significant change.
The difference between the two is not a rounding difference.
| Rating | What it measures | Where it is produced |
|---|---|---|
| STC | Sound through the separating assembly alone | Laboratory test of one assembly |
| ASTC | Sound through the separating assembly plus every flanking path around it | Field measurement, or calculation to ISO 15712-1 and the ISO 10848 series |
For the same pair of rooms, an ASTC value will always come in equal to or lower than the STC value. The laboratory number is a ceiling. It is not a result.
That reorders the design conversation. A slab cannot be compliant on its own, and no plant can sell a compliant slab. The flanking walls, the junction details and the slab together produce a number, and the walls carry more of it than most specs admit.
The published ratings for grouted hollow core
NRC Construction calculated standard scenarios for hollow core floors in a report prepared for the Canadian Precast/Prestressed Concrete Institute, report A1-012467.1, dated 28 March 2018. The scenarios use 203 mm hollow core slabs fully grouted at the joints between adjacent slabs, with 190 mm concrete masonry walls at 238 kg/m2.
Side-by-side rooms, where the masonry wall separates the units and the floor and ceiling are flanking paths:
| Slab mass with grout | Topping | Carpet | ASTC |
|---|---|---|---|
| 344 kg/m2 | None | None | 47 |
| 305 kg/m2 | None | None | 47 |
| 305 kg/m2 | 25.4 mm underlayment poured on the slab | None | 47 |
| 305 kg/m2 | 25.4 mm underlayment poured on the slab | 6 mm carpet on 8 mm underpad | 47 |
| 273 kg/m2 | None | None | 47 |
One room above the other, where the hollow core floor is the separating assembly and the masonry walls flank:
| Slab mass with grout | Topping | Carpet | ASTC |
|---|---|---|---|
| 344 kg/m2 | None | None | 54 |
| 305 kg/m2 | None | None | 51 |
| 305 kg/m2 | 25.4 mm underlayment poured on the slab | None | 52 |
| 305 kg/m2 | 25.4 mm underlayment poured on the slab | 6 mm carpet on 8 mm underpad | 52 |
| 273 kg/m2 | None | None | 49 |
Read the two tables together and the structure of the problem appears.
Stacked rooms pass with margin. The hollow core floor is doing the work, and the heaviest slab in the set reaches 54. Side-by-side rooms land on 47 in every case, including the heaviest slab and including both toppings. Horizontally, the floor is a flanking path, and a flanking path cannot be improved past the wall it runs around.
The report states the expectation plainly for the horizontal case: walls at 238 kg/m2 with grouted floors of at least 273 kg/m2 are expected to reach 47 or higher, with bare, unpainted walls and floors and no added ceiling lining. Nothing is held in reserve.
Side-by-side 47 is a result with no margin, and that is a design instruction
Every side-by-side scenario in the published set sits exactly on the requirement.
Three consequences follow for a multi-family floor plate.
A heavier slab buys nothing horizontally. Moving from 273 kg/m2 to 344 kg/m2 moves the stacked rating from 49 to 54 and leaves the side-by-side rating at 47. Specifying mass to solve a horizontal complaint is money spent on the wrong path.
The scenarios are geometry-specific. The report is explicit that deviations from the dimensions shown in the standard scenarios can change the ratings. A real floor plate with different room dimensions is not covered by the published number, and on a result that already has no margin, a change in the wrong direction has nowhere to go.
Lighter flanking walls are outside the published set. The scenarios assume 190 mm concrete masonry at 238 kg/m2. The report does not say what a lighter wall does, and it is not a number to assume. If the separating wall is not masonry at that mass, the horizontal case needs its own calculation.
Where an acoustical consultant is on the project, this is the line item to hand them: the horizontal pairs, with the actual room dimensions and the actual wall construction.
The topping is a structural and levelling decision, not the acoustic fix
A poured topping is often sold as the sound answer. The published numbers do not support that.
| Change | Side-by-side | Stacked |
|---|---|---|
| No topping, 305 kg/m2 slab | 47 | 51 |
| Add 25.4 mm underlayment | 47 | 52 |
| Add underlayment and carpet on underpad | 47 | 52 |
A 25.4 mm underlayment moves the stacked rating by one point and the side-by-side rating by none. Carpet on an underpad adds nothing to either in the airborne case.
Specify the topping for the reasons it earns its place: diaphragm action, levelness, embedded services, finish flooring tolerances. Do not specify it to recover an airborne shortfall, and do not let it stand in for an impact noise strategy, which is a separate rating and outside this article.
Grout at the keyways is part of the acoustic assembly
Every scenario in the report assumes slabs fully grouted at the joints between adjacent slabs. The report gives the mass per unit area both ways.
| Nominal condition | Mass with grout | Mass without grout |
|---|---|---|
| Lightest slab in the set | 273 kg/m2 | 269 kg/m2 |
| Middle slab in the set | 305 kg/m2 | 301 kg/m2 |
| Heaviest slab in the set | 344 kg/m2 | 338 kg/m2 |
The mass difference is small. The published ratings are not offered for the ungrouted condition at all, and the lightest grouted slab in the set is the floor of the whole table. An ungrouted keyway is also an open seam between units.
Treat keyway grouting as a scheduled, inspected item on an acoustic separation, not as a trade detail settled in the field.
Confirming the clause before it reaches a spec
The acoustical requirement sits in the model code text, and that text is published by the National Research Council rather than posted as free-standing clauses. The edition in force is a provincial fact, and the clause number is an edition-specific fact. Confirm both before the number is quoted in a submittal.
| Step | Who does it | What to ask for |
|---|---|---|
| Confirm the edition in force | Prime consultant | The building code edition and printing currently declared in force in Alberta, with the in-force date |
| Pull the clause | Prime consultant or code consultant | The sound transmission article for dwelling unit separations in that edition, by article and sentence number |
| Fix the compliance route | Design team | Whether the project will demonstrate ASTC by calculation to ISO 15712-1, by field measurement, or by a prescriptive route in Part 9 |
| Scope the horizontal case | Acoustical consultant | A calculation for the side-by-side room pairs using actual dimensions and actual wall construction |
| Confirm what the floor must deliver | Design team with the plant | Slab depth, required mass per unit area, grouting requirement, topping thickness if any |
The figures in this article are from the 2018 NRC report and from the 2015 model code change that introduced ASTC. We have not reproduced an article number here, because we did not read the clause in the edition in force. Confirm the clause; the published ratings above do not change with it.
Lead time: what drives it
We quote lead time against the drawing package in hand. The drivers, in order of weight:
- Slab depth and the required mass per unit area, and whether current beds produce it.
- Total area, panel widths and the erection sequence.
- Opening and penetration schedule, which drives the voids and the end details.
- Bearing details and connection hardware at walls and beams.
- Whether a topping is in scope, and who places it.
- Crane access, set dates and the stacking plan on site.
Decades of casting hollow core for Alberta floor plates says the schedule follows the opening schedule. Mass is a bed decision. Penetrations are a drawing decision, and they arrive late.
Ordering: what the plant needs
Send this and we can quote.
- Building type, number of storeys and occupancy of the units above and below.
- Floor plate drawings with spans, bearing lines and panel layout if one exists.
- Required slab depth, or the span and loads so we can propose one.
- Required mass per unit area, where an acoustic calculation has set one.
- Superimposed dead and live loads, including partition and finish loads.
- Topping thickness and whether it is composite, and who places it.
- Keyway grouting requirement and who grouts.
- Fire resistance rating required for the floor assembly.
- Opening and penetration schedule with sizes and locations.
- Bearing conditions, seat details and connection hardware at every support.
- Erection access, crane position and the set date.
- The acoustical consultant’s report, where one exists, and the assemblies it assumed.
Where this article stops
This article covers airborne sound ratings for 203 mm grouted precast concrete hollow core floors in multi-unit residential buildings in Alberta, and the fabrication information we need to quote them. It does not design your floor and it does not replace an acoustical consultant. It does not cover impact sound, impact insulation class or apparent impact insulation class, which are separate ratings with separate test methods. It does not cover other slab depths, ungrouted assemblies, lightweight or wood-frame flanking walls, or added ceiling linings, none of which appear in the published scenarios. It does not cover structural design, span tables, diaphragm design or fire resistance ratings, which are covered in our notes on precast concrete design. It does not cover mechanical and electrical noise sources, elevator shafts or refuse chutes, which run on their own requirements. And it does not cover any jurisdiction outside Alberta.
FAQ
What sound rating does hollow core need in Alberta? The separation between dwelling units has to meet an apparent sound transmission class of 47, or a laboratory sound transmission class of 50. Confirm the clause in the building code edition currently in force.
Does an 8 in. hollow core floor meet ASTC 47? In the NRC standard scenarios, grouted 203 mm hollow core with 190 mm concrete masonry walls at 238 kg/m2 reaches 47 in side-by-side rooms and 49 to 54 in stacked rooms, with no topping and no added ceiling. Your room dimensions and wall construction can change that.
Is ASTC the same as STC? No. STC is a laboratory rating of one assembly. ASTC includes the flanking paths around it, so for the same rooms it comes in equal to or lower than the STC.
Will a concrete topping raise the sound rating? Barely. In the published scenarios a 25.4 mm underlayment moved the stacked rating from 51 to 52 and left the side-by-side rating at 47. Specify a topping for structural and levelling reasons.
Do the keyways have to be grouted? The published ratings all assume slabs fully grouted at the joints between adjacent slabs. Ungrouted assemblies are not covered.
Who is responsible for the ASTC number? The design team. The plant supplies a slab to a specified depth, mass and grouting requirement; the rating is produced by the assembled separation.
Get a spec sheet, a drawing and a lead time
Send the floor plate, the span and loads, and the acoustic requirement your consultant has set. We will return a spec sheet, a general arrangement drawing, a lead time and a price by quantity. Start at Omega Precast residential solutions, or send drawings straight to estimating and preconstruction. Multi-unit projects usually need the stairwells on the same schedule; see our notes on precast stairs for multi-family projects and on precast concrete for affordable housing in Alberta.